system.tag.writeToTag
This function is used in Python Scripting.
Description​
Writes a value to a tag. If suppressErrors is true, error messages on failed writes will not be shown.
Client Permission Restrictions​
This scripting function has no Client Permission restrictions.
Syntax​
system.tag.write(tagPath, value, [suppressErrors])
- Parameters
- String
tagPath
- The path of the tag to write to. - Object
value
- The value to write. - Boolean
suppressErrors
- A flag indicating whether or not to suppress errors. [optional]
- String
- Returns
- int - 0 if the write failed immediately, 1 if it succeeded immediately, and 2 if it is pending.
- Scope
- All
Code Examples​
Code Snippet
# This code would go on a property change event for a numeric text field to calculate and write a value to a tag.
if event.propertyName == intValue:
calcValue = event.newValue * 2.5
system.tag.writeToTag("Tanks/tankHiSP",calcValue)