Vision - Moving Analog Indicator
Component Palette Icon:
The Moving Analog Indicator displays an analog value as an arrow pointing at a bar with segments showing the desired operating range, low and high alarm ranges, and interlock ranges.
To switch the Moving Analog Indicator between a horizontal vs vertical orientation, change the size so that it is either wide or tall. Setup of this component involves setting the ranges and binding the Process Value property to a Tag's value.
Properties​
| Property | Description | Property Type | Scripting | Category | 
|---|---|---|---|---|
| Border | The border surrounding this component. Options are No border, Etched (Lowered), Etched (Raised), Bevel (Lowered), Bevel (Raised), Bevel (Double), and Field Border. Note: The border is unaffected by rotation. | Border | .border | Common | 
| Cursor | The mouse cursor to use when hovering over this component. Options are: Default, Crosshair, Text, Wait, Hand, Move, SW Resize, or SE Resize. | int | .cursorCode | Common | 
| Desired High | The upper value of the desired operating range. | Double | .desiredHi | Data | 
| Desired Low | The lower value of the desired operating range. | Double | .desiredLo | Data | 
| Desired Range Color | The color of the desired range. Can be chosen from color wheel, chosen from color palette, or entered as RGB or HSL value. See Color Selector. | Color | .desiredRangeColor | Appearance | 
| High Alarm | The value above which is a high alarm. | Double | .hiAlarm | Data | 
| High High Alarm | The value above which is a high-high alarm. | Double | .hihiAlarm | Data | 
| High Interlock | The value above which an interlock will be activated. | Double | .hiInterlock | Data | 
| Inactive Alarm Color | The color of inactive alarm range. See Color Selector. | Color | .inactiveAlarmColor | Appearance | 
| Interlock Color | The color of the interlock range. See Color Selector. | Color | .interlockColor | Appearance | 
| Level 1 Alarm Color | The color of an active level 1 alarm (Hi-Hi or Lo-Lo). See Color Selector. | Color | .level1AlarmColor | Appearance | 
| Level 2 Alarm Color | The color of an active level 2 alarm (Hi or Lo). See Color Selector. | Color | .level2AlarmColor | Appearance | 
| Low Alarm | The value below which is a low alarm. | Double | .loAlarm | Data | 
| Low Interlock | The value below which an interlock will be activated. | Double | .loInterlock | Data | 
| Low Low Alarm | The value below which is a low-low alarm. | Double | .loloAlarm | Data | 
| Mouseover Text | The text that is displayed in the tooltip which pops up on mouseover of this component. | String | .toolTipText | Common | 
| Name | The name of this component. | String | .name | Common | 
| Process Value | The current value of the process. | Double | .processValue | Data | 
| Quality | The data quality code for any Tag bindings on this component. | QualityCode | .quality | Data | 
| Range Fill | The background color of the range strip. See Color Selector. | Color | .rangeFill | Appearance | 
| Range High | The overall high value for the display. | double | .rangeHi | Data | 
| Range Low | The overall low value for the display. | double | .rangeLo | Data | 
| Range Stroke | The stroke color for the range strip. See Color Selector. | Color | .rangeStroke | Appearance | 
| Reverse Indicator | Put the indicator triangle on the other side of the track. | boolean | .reverseIndicatorLocation | Appearance | 
| Setpoint Fill | The fill color of the setpoint indicator. See Color Selector. | Color | .setpointFill | Appearance | 
| Setpoint Stroke | The stroke color of the setpoint indicator. See Color Selector. | Color | .setpointStroke | Appearance | 
| Setpoint Value | The current value of the setpoint. | Double | .setpointValue | Data | 
| Show Value | Show the current value above or beneath the value indicator. | boolean | .showValue | Appearance | 
| Stroke Width | The stroke width for lines drawn. | float | .strokeWidth | Appearance | 
| Styles | Contains the component's styles | Dataset | .styles | Appearance | 
| Value Color | The color of the value label. See Color Selector. | Color | .color | Appearance | 
| Value Font | The font for the value label. | Font | .font | Appearance | 
| Value Format | The string format for the value, if it is shown. | String | .valueFormat | Appearance | 
| Value Indicator Fill | The fill color of the value indicator. See Color Selector. | Color | .valueFill | Appearance | 
| Value Indicator Stroke | The stroke color of the value indicator. See Color Selector. | Color | .valueStroke | Appearance | 
| Visible | If disabled, the component will be hidden. | boolean | .visible | Common | 
Deprecated Properties​
| Property | Description | Property Type | Scripting | Category | 
|---|---|---|---|---|
| Data Quality | The data quality code for any Tag bindings on this component. | int | .dataQuality | Deprecated | 
Scripting​
Component Functions​
This component does not have component functions associated with it.
Extension Functions​
This component does not have extension functions associated with it.
Event Handlers​
Event handlers allow you to run a script based off specific triggers. See the full list of available event handlers on the Component Events page
Customizers​
Examples​
Default Moving Analog Indicator Expanded Horizontally​
Stylized Moving Analog Indicator​
| Property Name | Value | 
|---|---|
| Show Value | True | 
| Reverse Indicator | True | 
| Stroke Width | 0.0 |