executeUpdateQuery
This function is used by Ignition's Expression language.
Description​
note
This function is only available in Transaction Group Expression Items and Expression Tags.
Executes an update query using the given ConnectionName (or the default connection it omitted) and returns the number of rows effected.
Syntax​
executeUpdateQuery(query[, connectionName])
Parameters
string query - The query to execute.
string connectionName - Optional. The name of the database connection.
Results
- int - The number of rows affected.
Examples​
Code Snippet
executeUpdateQuery("UPDATE table SET columnName1 = 15.89 WHERE index = 4", "MySQLConnection") //would return a 1 and update the table.