getDatasetValueByName
This feature was removed from Ignition in version 8.0.0
This function is used by Ignition's Expression language.
Description​
note
This function is only available in Transaction Group Expression Items and Expression Tags.
Retrieves data from a global variable DatasetName created using the ExecuteQuery function.
Syntax​
getDatasetValueByName(datasetName, row, column, fallback)
Parameters
string datasetName - The name of the dataset created using the executeQuery function.
int row - The row index.
string column - The name of the column.
Object fallback - A fallback value if the lookup fails.
Results
- Object - The value at the given row index and column name. They type returned matches the type of the value selected.
Examples​
For example, suppose you had a dataset called 'MyResult' with this information in it:
ProductCode | Quantity | Weight |
---|---|---|
BAN_002 | 380 | 3.243 |
BAN_010 | 120 | 9.928 |
APL_000 | 125 | 1.287 |
FWL_220 | 322 | 7.889 |
Code Snippet
getDatasetValueByName("MyResult", 0, "Quantity", -1) //would return 380
getDatasetValueByName("MyResult", 1, "Weight", -1) //would return 9.928
getDatasetValueByName("MyResult", 0, "Color", -1) //would return -1 because there is no Color column and it reverts to the fallback value.