Skip to main content
Version: Deprecated Pages

executeUpdateQuery

This feature was removed from Ignition in version 8.0.0

This function is used by Ignition's Expression language.

Description​

note

This function is only available in Transaction Group Expression Items and Expression Tags.

Executes an update query using the given ConnectionName (or the default connection it omitted) and returns the number of rows effected.

Syntax​

executeUpdateQuery(query[, connectionName])

  • Parameters

    • string query - The query to execute.

    • string connectionName - Optional. The name of the database connection.

  • Results

    • int - The number of rows affected.

Examples​

Code Snippet
executeUpdateQuery("UPDATE table SET columnName1 = 15.89 WHERE index = 4", "MySQLConnection") //would return a 1 and update the table.