Remote Gateway Notification

Inductive University

Remote Alarms

Watch the video

The Remote Gateway Notification profile allows one Gateway to send alarm notifications using a notification profile hosted on a different Gateway in the same Gateway Network. This lets you centralize email, SMS, and voice delivery infrastructure while distributing alarm generation across remote sites.

This is especially useful when remote Gateways lack direct access to email servers or telephony hardware. The remote Gateway triggers the alarm; the central Gateway handles the delivery.

info

The Alarm Notification module must be installed and licensed on all participating Gateways. However, notification-specific modules (like SMS or Voice) are only required on the Gateway that executes the notification.

info

Both Gateways must be connected via the Gateway Network.

Create a Remote Gateway Notification Profile​

Follow these steps to create a Remote Gateway Notification Profile.

  1. In the Gateway, go to Platform > Alarming > Notification.

  2. Click Create Profile +.

  3. Select Remote Gateway Notification, then click Next.

    Remote gateway option

  4. Enter the required values using the following example:

    • Name: Remote
    • Gateway: IP address or name of the remote Gateway.
    • Notification Profile: Email 1

    Remote gateway profile setup

  5. Click Create Alarm Notification Profile.

  6. The profile will appear in the list and show a status of Connected or Registered once the connection is successful.

Once created, this profile can be used in any local pipeline or notification block.

Remote Gateway Notification Profile Settings​

General​

Property NameDescription
NameName of the notification profile.
DescriptionOptional description of the profile.
EnabledWhether the profile is currently active.

Remote Gateway​

Property NameDescription
GatewayIP address or hostname of the remote Gateway in the Gateway Network.
Notification ProfileName of the alarm notification profile on the remote Gateway to be used for sending notifications.

Advanced​

Property NameDescription
Retry DelayTime to wait (in milliseconds) before retrying a failed synchronization with the remote Gateway. Default: 10000.
Max Queued Alarm TransitionsMaximum number of alarm transitions to hold in the queue while the remote Gateway is unavailable. Default: 10000.

Assign a Remote Pipeline to an Alarm​

After creating the profile, you can assign a remote pipeline to an alarm directly from the Tag Editor.

  1. In the Designer, open the Tag Browser and double-click the tag you want to configure.

    Tag browser open

  2. Scroll to the Alarms section and click the Edit icon for the alarm.

  3. In the alarm editor, scroll to the Notification Settings section.

  4. Under Active Pipeline, select a pipeline from the remote Gateway (e.g., Remote/Pipeline1).

  5. Click Commit to save your changes.

    Assign remote pipeline

Once saved, the tag will send alarm notifications using the remote Gateway’s pipeline.

info

Only the Gateway executing the notification must have the necessary notification modules installed (Email, SMS, or Voice).

You can also use the profile in a Notification Block within an alarm pipeline.