Skip to main content
Version: 2027.02 Beta
View as Markdown

system.historian.deleteAnnotations

This function is used in Python Scripting.

Description​

Deletes desired annotations from the specified historian.

Client Permission Restrictions​

This scripting function has no Client Permission restrictions.

Syntax​

system.historian.deleteAnnotations(paths, storageIds)

Parameters​

TypeParameterDescription
ListpathsA list of historical paths associated with the annotations. See Path Syntax for more information on recommended syntax.
ListstorageIdsA list of annotation storage IDs to be used for deleting.

Returns​

List - A list of QualityCode objects. The quality code will indicate success or failure, and if successful, the storage ID of the annotation will have been deleted.

Scope​

Gateway, Vision Client, Perspective Session

Code Examples​

Code Snippet
# Delete a previously stored annotation and log an info level formatted message.   

paths = ["histprov:MySQL:/sys:gw1:/prov:default:/tag:history_200"]
storageIds = ["1f001108-5689-4b2a-b995d360250a"]
result = system.historian.deleteAnnotations(paths, storageIds)

system.util.getLogger('HistorianTest: deleteAnnotations').info(str(result))